Step-by-step debugging procedures for DL, DD and DJ evaporators and condensers FNH, FNH,FNV,FNVT.
Debugging is a decisive stage, which determines the future performance of any refrigeration equipment. Hasty or incomplete completion of it is the reason for many failures in the months after the work is completed. The test sequence of DL, DD and DJ evaporators and FNH, FNH,FNV,FNVT capacitors is logical.
First of all, there is no voltage with the whole installation, and general mechanical inspection is carried out. Check the fixation of all equipment, tighten the folding fins of evaporator and condenser, and comb them with fins. Check the free manual rotation of each fan without friction or obstacles. Check the slope and manual operation of the evaporator drainage system.
Step 2: Check the cooling system. Make sure that all protective covers are removed only during welding. Visually inspect all welds and joints for visible defects. Carry out pressure seal test according to applicable regulations to detect leakage before loading refrigerant.
Third, the vacuum of the cooling circuit. Realize deep vacuum and keep it for necessary time to remove moisture and air trapped in the pipeline, evaporators DL,DD,DJ and condensers FNH,FNV,FNVT. Do not skip this operation, internal humidity will cause ice blockage in the expansion valve.
Fourth, coolant. Load according to project data, not just based on pressure readings. Proper amount of refrigerant is very important to obtain proper superheat and subcooling values.
Fifth, start the equipment, start the system, and wait for a stable working state. Do not adjust the expansion valve in the first few minutes. Once the room temperature is stable, measure and adjust the reference values of overheating in the evaporator and supercooling in the condenser.
Sixth: check the complete operation of all accessories: prestress, thawing cycle, drainage heating resistance, condensing fan adjustment, drainage siphon. Simulate the activation security element to confirm your response.
Seventh: Record all startup values: pressure, temperature, overheating, supercooling and power consumption readings in the technical report. This document can be used as a reference for future maintenance and fault diagnosis.
According to the statistics of xindacool, about 21% of the faults occurred in the first year of operation were due to incomplete debugging or hasty completion.
FAQ
What checks should be made before applying voltage to the equipment? Mechanical inspection, fan manual rotation, blade inspection and drainage.
What is the purpose of vacuum in cooling circuit? Eliminate air and moisture, which may cause subsequent valve and compressor failures.
Is it only necessary to start the equipment to adjust the expansion valve? No, you must wait for the system to reach a stable operating condition.
What do you need to simulate during startup? Safe prefabrication, thawing cycle and automatic adjustment system.
Why is it important to save the startup log? They can be used as a reference for comparing values in future maintenance reviews.
Key words: refrigeration system startup, vacuum refrigeration circuit, waterproof test, expansion valve adjustment, startup report, DL series air cooler, DD series air cooler, DJ series air cooler, FNH condenser, FNV condenser, FNVT condenser.